YASKAWA ELECTRIC SIEP C730600 69A 1000-Series Option SI-EP3 Technical Manual

Option High Priority Alarm Codes

These codes are transmitted as Manufacturer Specific Diagnostic high priority alarms that can be seen in the PLC
configuration software. These high priority codes are the same codes that appear in the drive manual, except with an
offset of 0x1000.

Table 24 PROFINET Option High Priority Alarm Codes

Drive Alarm

Code

(Hex)

<1>

Description

Corrective Action

1000

None

1001

DC Bus Fuse Open (PUF)

Output Transistor Failure. Replace the drive

1002

DC Bus Undervolt (Uv1)

Input power fluctuation too large

1003

CTL PS Undervolt (Uv2)

Cycle drive power and replace drive if fault continues

1004

MC Answerback (Uv3)

Cycle drive power and replace drive if fault continues

1005

Short Circuit (SC)

• Check drive wiring
• Cycle drive power and replace drive if fault continues.

1006

Ground Fault (GF)

Check for motor and/or cable damage

1007

Over Current (oC)

Check motor, motor load and accel/decel rates

1008

DC Bus Overvolt (oV)

• Check incoming voltage
• Check deceleration time

1009

Heatsink Overtemp (oH)

• Check ambient temperature
• Check drive cooling fan

100A

Heatsink Max Temp (oH1)

Check drive cooling fan

100B

Motor Overload (oL1)

• Check the load, accel/decel and cycle times
• Check motor rated current (E2-01)

100C

Inv Overload (oL2)

• Check the load, accel/decel and cycle times
• Check drive rating

100D

Overtorque Det 1 (oL3)

• Check L6-02 and L6-03 settings
• Check system mechanics

100E

Overtorque Det 2 (oL4)

• Check L6-05 and L6-06 settings
• Check system mechanics

100F

DynBrk Transistor (rr)

Cycle drive power and replace drive if fault continues

1010

DynBrk Resistor (rH)

Check load, operating speed and deceleration time

1011

External Fault 3 (EF3)

• Multifunction digital input set to external fault
• Circuit at terminal is closed

1012

External Fault 4 (EF4)

1013

External Fault 5 (EF5)

1014

External Fault 6 (EF6)

1015

External Fault 7 (EF7)

1016

External Fault 8 (EF8)

1017

Heatsink Fan (FAn)

Check drive cooling fan

1018

Overspeed Det (oS)

• Check reference and reference gain
• Check F1-08 and F1-09 settings

1019

Speed Deviation (dEV)

• Check load, accel/decel times and system mechanics
• Check F1-10 and F1-11 settings

101A

PGo Open (PGo)

Check PG card connections

101B

Input Phase Loss (PF)

Excessive input voltage fluctuation

101C

Output Phase Loss (LF)

• Check for broken wire/loose terminals
• Check motor rating

101D

None

101E

Operator Disconnected (oPr)

Reconnect the digital operator

101F

EEPROM R/W Error (Err)

Cycle drive power and replace drive if fault continues

1020

None

1021

Comm Error (bUS)

• Check network cable connections.
• Check 24 Vdc power supply voltage

1022

Check option installation and connections.

1023

Cycle drive power and replace option or drive if fault continues.

1024