6 Option Related Drive Parameters

YASKAWA SIEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Technical Manual

19

6

Option Related Drive Parameters

The following parameters are used to set up the drive for operation with the option. Parameter setting instructions can be
found in the drive product manual.

Confirm proper setting of the all parameters in

Table 6

before starting network communications.

Table 6 Parameter Settings

No.

Name

Description

Default

b1-01

<1>

Frequency Reference Selection

Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse Input (Terminal RP)

1

(Set to 3 for

PROFINET)

b1-02

<1>

Run Command Selection

Selects the run command input source.
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus communications
3: Option PCB

1

(Set to 3 for

PROFINET)

F6-01

Operation Selection after
Communications Error

Determines drive response when a bUS error is detected during
communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

4: Alarm (d1-04)

<3>

5: Alarm Ramp to Stop

<3>

1

F6-02

External Fault Detection
Conditions (EF0)

Sets the condition for external fault detection (EF0).
0: Always detected
1: Detected only during operation

0

F6-03

Stopping Method for External
Fault from Communication Option
Board

Determines drive response for external fault input (EF0) detection during
communication.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

1

F6-07

NetRef/ComRef Selection
Function

0: Multi-step speed reference disabled
1: Multi-step speed reference allowed

1

F6-08

Reset Communication Related
Parameters

Determines if communication-related parameters F6-†† and F7-†† are
set back to original default values when the drive is initialized using
parameter A1-03.
0: Do not reset F6-†† and F7-†† parameters
1: Reset F6-†† and F7-†† parameters
Note: Setting this parameter does not affect communication-related
parameters.

0

F6-14

<3>

bUS Error Auto Reset

0: Disabled
1: Enabled

0

F7-01

to

F7-04

IP Address

Sets static IP address of the SI-EP3 option when parameter F7-13=0.
Note: Parameter F7-01 sets the most significant octet.

192 168 1 20

F7-05

to

F7-08

Subnet Mask

Sets static Subnet Mask of network connection.
Note: Parameter F7-05 sets the most significant octet

255 255 255 0

F7-09

to

F7-12

Gateway Address

Sets static Gateway address of network connection.
Note: Parameter F7-09 sets the most significant octet.

192 168 1 1