10 Troubleshooting

52

YASKAWA SIEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Technical Manual

LED Operator Display

Fault Name

oFA00

Option fault.
Option is not properly connected.

Cause

Possible Solution

Non-compatible option connected to the drive

Connect an option that is compatible with the drive.

LED Operator Display

Fault Name

oFA01

Option fault.
Option is not properly connected.

Cause

Possible Solution

Problem with the connectors between the drive
and option

Turn the power off and check the connectors between the drive and option.

LED Operator Display

Fault Name

oFA03

Option fault.
Option self-diagnostics error.

Cause

Possible Solution

Option hardware fault

Replace the option.

LED Operator Display

Fault Name

oFA04

Option fault.
Option flash write mode.

Cause

Possible Solution

Option hardware fault

Replace the option.

LED Operator Display

Fault Name

to

oFA30 to oFA43

Option Fault (Port A).

Communication ID error.

Cause

Possible Solution

Option hardware fault

Replace the option.

LED Operator Display

Fault Name

oFb00

Option fault (CN5-B).
Non-compatible option is connected.

Cause

Possible Solution

Non-compatible option connected to the drive.

Connect the correct option to CN5-A.

LED Operator Display

Fault Name

oFb02

Option fault (CN5-B).
Two of the same options are connected at the same time.

Cause

Possible Solution

Options AI-A3 or DI-A3 were connected to the
CN5-B port while an option was already
connected to CN5-A.

• Only one type of AI-A3 or DI-A3 option can be connected to the drive.
• The SI-EP3 option can only be connected to CN5-A.