10 Troubleshooting

YASKAWA SIEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Technical Manual

55

„

Option Fault Monitors U6-98 and U6-99

The option can declare error/warning conditions via drive monitor parameters on the drive digital operator as shown in

Table 32

.

Table 32 Option Fault Monitor Descriptions

Two drive monitor parameters, U6-98 and U6-99 assist in network troubleshooting:

• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present option SI-EP3 status. U6-99 is cleared upon a network-issued fault reset and upon

power-up.

If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99
stores the new fault status value.

„

Option Compatibility

A limited number of options may be simultaneously connected to the drive depending on the type of option. Refer to

Table 33

for more information. More details can be found in the Options and Peripheral Devices chapter of the drive

Technical Manual.

Table 33 Option Installation Compatibility

Fault Condition

Fault Declared

Status Value

(U6-98/U6-99)

Description

No Fault

n/a

0

No faults.

Force Fault

EF0

3

Network sent a message to force this node to the fault state.

Network Link Down

BUS ERROR

1300

No network link to option board.

Network Failure

BUS ERROR

1301

Connection with PLC Timeout.

Default MAC Address

None

1303

Factory default MAC Address programmed into the option. Return for
reprogramming.

No IP Address

None

1304

No IP Address has been programmed into the option.

No Station Name

None

1305

No Station Name has been programmed into the option.

Config Error

None

1306

Configuration error on power-up.

Init. Failure

None

1307

Initialize error on power-up.

Permanent
Communication Loss

BUS ERROR

1308

Fatal error in MAC/PHY hardware, requires power cycle to recover.

Option

<1> When installed in CN5-A, the AI-A3 and DI-A3 options can be used to set the frequency reference or replace the drive analog inputs with higher

resolution. When installed in CN5-B or CN5-C, these options can only be used for monitoring; their input levels will be displayed in U1-17 or

U1-21 to U1-23.

<2> Use the CN5-C connector when connecting only one option to the drive; use both CN5-B and CN5-C when connecting two options.

Connector

Number of Possible Options

SI-C3, SI-N3, SI-P3, SI-S3, SI-EP3, SI-EN3, SI-EM3

<1>

CN5-A

1

PG-B3, PG-X3

CN5-B, C

2

<2>

DO-A3, AO-A3, AI-A3, DI-A3

CN5-A, B, C

1