10 troubleshooting, Drive-side error codes, Troubleshooting – Yaskawa PROFINET User Manual

Page 51

Advertising
background image

10 Troubleshooting

YASKAWA SIEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Technical Manual

51

10

Troubleshooting

‹

Drive-Side Error Codes

Drive-side error codes appear on the drive digital operator. Causes of the errors and corrective actions are listed in

Table 30

. For additional error codes that may appear on the drive digital operator, refer to the drive Technical Manual.

„

Faults

Both bUS (SI-EP3 option communication error) and EF0 (External fault input from the SI-EP3 option) can appear as an
alarm or as a fault. When a fault occurs, the digital operator ALM LED remains lit. When an alarm occurs, the ALM LED
flashes.

If communication stops while the drive is running, use the following questions as a guide to help remedy the fault:

• Is the option properly installed?
• Is the communication line properly connected to the option? Is it loose?
• Is the controller program working? Has the controller/PLC CPU stopped?
• Did a momentary power loss interrupt communications?

Table 30 Fault Display and Possible Solutions

LED Operator Display

Fault Name

bUS

Option Communication Error.

• After establishing initial communication, the connection was lost
• Only detected when the run command or frequency reference is assigned to the option

(b1-01 = 3 or b1-02 = 3)

Cause

Possible Solution

Master controller (PLC) has stopped
communicating

• Check that power is supplied to the PLC
• Check that PLC is not in program mode

Communication cable is not connected properly

• Check for faulty wiring
• Correct any wiring problems

A data error occurred due to noise

• Check the various options available to minimize the effects of noise
• Counteract noise in the control circuit, main circuit, and ground wiring
• If a magnetic contactor is identified as a source of noise, install a surge absorber to the

contactor coil

• Make sure the cable used meets the PROFINET requirements
• Make sure the option ground wire is connected between option FE terminal and the drive

ground terminal connected to earth ground

Option is damaged

If there are no problems with the wiring and the error continues to occur, replace the option.

LED Operator Display

Fault Name

EF0

External fault input from option.
The alarm function for an external device has been triggered.

Cause

Corrective Action

An external fault is being sent from the upper
controller (PLC)

• Remove the cause of the external fault
• Reset the external fault input from the PLC device

Problem with the PLC program

Check the program used by the PLC and make the appropriate corrections.