10 Troubleshooting

54

YASKAWA SIEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Technical Manual

Figure 23

Figure 24 bUS Error Delay Timing Example

Related Parameters

Table 31 Parameters related to bUS Error Auto-Reset Functionality

No.

(Addr. Hex)

<2> If F6-01 is set to 3, then the drive will continue to operate when a bUS error is detected. Use caution and proper safety measures, when installing

an emergency stop switch.

<5> The availability of this feature/function depends on drive model, software version and Profinet firmware version. Refer to

Table 35

for specifics

relating to your drive.

Name

Description

Default

F6-01

(03A2)

Operation Selection after
Communications Error

Determines drive response when a bUS error is detected during
communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

4: Alarm (d1-04)

<5>

5: Alarm Ramp to Stop

<5>

1

F6-14

<5>

(03BB)

bUS Error Auto Reset

0: Disabled
1: Enabled

0

F7-16

<5>

(03F4)

Communication Loss Timeout

Sets the timeout value for communication loss detection in tenths of
a second.
A value of 0 disables the connection timeout.
Example: An entered value of 100 represents 10.0 seconds.
Note: A change to this parameter setting is not effective until main
power to the drive is cycled.

0.0

E86

&RQGLWLRQ

E86 (UURU

RQ GULYH

2XWSXW

)UHTXHQF\

E86 (UURU 'HOD\

) !  &RPP/RVV 7RXW

1HWZRUN

FRQQHFWLRQ
LQWHUUXSWHG

1HWZRUN

FRQQHFWLRQ

UHWXUQV

)

 VHF

)

 VHF

)

 VHF