5 Installation Procedure

20

YASKAWA ELECTRIC TOBP C730600 54A V1000 Option CompoNet Installation Manual

4.

On IP20/Open-Chassis models, connect the drive-side of the ground wire to the
drive ground terminal.

Note: The four different ground wires packaged with the option connect the option to different drive

models. Select the proper ground wire depending on drive size.

Figure 7

Figure 7 Connect the Ground Wire on an IP20/Open-Chassis Drive

5.

For IP20/Open-Chassis models, go to Step

9.

on page

23

.

6.

For IP20/NEMA Type 1 Enclosure models CIMR-V

……

A

…………

F, loosen the screw

on the front of the NEMA Type 1 terminal cover and remove it from the drive. Refer

to

Figure 8

for details

Refer to

Figure 9

for drive models CIMR-V

…

BA0006F to BA0018F, 2A0008F to

2A0069F, and 4A0001F to 4A0038F, which require removing the plastic terminal

cover prior to removing NEMA Type 1 terminal cover.

Note: Installing the option on an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection

while maintaining IP20 conformity.

Figure 8

Figure 8 Remove the NEMA Type 1 Terminal Cover

Ground terminal

Ground wire

Ground wire

Drive-side
connector
Screw size:
M3.5 to M6

Option unit
connector
Screw size: M3