8 Configuring CompoNet Messaging

36

YASKAWA ELECTRIC TOBP C730600 54A V1000 Option CompoNet Installation Manual

Drive Operation on CompoNet

Polled Assemblies Quick Reference

Refer to the CompoNet Option SI-M3/V Technical Manual for details on polled assemblies

and other message types.

Output Assemblies/Drive Consumes

Input Assemblies/Drive Produces

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

20

CompoNet

Basic

Speed

Control

0

-

-

-

-

-

Fault

Reset

-

Run Fwd

1

-

2

Speed Reference (Low Byte)

3

Speed Reference (High Byte)

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

21

CompoNet

Extended

Speed

Control

0

-

Net Ref

Net Ctrl

-

-

Fault

Reset

Run

Rev

Run

Fwd

1

-

2

Speed Reference (Low Byte)

3

Speed Reference (High Byte)

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

70

CompoNet

Basic

Speed

Control

0

-

-

-

-

-

Running 1

-

Faulted

1

-

2

Speed Actual (Low Byte)

3

Speed Actual (High Byte)

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

71

CompoNet

Extended

Speed

Control

0

At Speed

Ref from

Net

Ctrl from

Net

Ready

Running 2

(REV)

Running 1

(FWD)

Warning

Faulted

1

State

2

Speed Actual (Low Byte)

3

Speed Actual (High Byte)