7 Troubleshooting

32

YASKAWA ELECTRIC TOBP C730600 54A V1000 Option CompoNet Installation Manual

Digital Operator Display

Fault Name

EF0

External Fault Input from the Option

The alarm function for an external device has been triggered.

Cause

Corrective Action

An external fault is being sent from
the master.

Remove the cause of the external fault.
Reset the external fault input from the master device.

Problem with the master program.

Check the program used by the master and make the appropriate corrections.

Digital Operator Display

Fault Name

oFA00

Option Fault

Option is not properly connected.

Cause

Possible Solution

Non-compatible option connected to
the drive.

Use only compatible options.

Digital Operator Display

Fault Name

oFA01

Option Fault

Option is not properly connected.

Cause

Possible Solution

Problem with the connector between
the drive and option.

Turn the power off and check the connectors between the drive and option.

Digital Operator Display

Fault Name

oFA03

Option Fault

Option self-diagnostics error.

Cause

Possible Solution

Option hardware fault.

Replace the option.

Digital Operator Display

Fault Name

oFA04

Option Fault

Option Flash write mode

Cause

Possible Solution

Option hardware fault.

Replace the option.