YASKAWA ELECTRIC TOBP C730600 54A V1000 Option CompoNet Installation Manual

6 Related Parameters

6

Related Parameters

The following parameters are used to set up the drive for operation with the option.
Confirm proper setting of parameters in

Table 9

before starting network communications.

Table 9 Related Parameters

No.

(Addr. Hex)

Name

Description

Values

b1-01

(180)

<1>

Frequency Reference
Selection

Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse Input (Terminal RP)

Default: 1
Range: 0 to 4
(Set to 3 for
CompoNet only)

b1-02

(181)

<1>

Run Command
Selection

Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S†
2: MEMOBUS/Modbus communications
3: Option PCB

Default: 1
Range: 0 to 3
(Set to 3 for
CompoNet only)

F6-01
(3A2)

Operation Selection
after
Communications
Error

Determines drive response when a bUS error is detected
during communications with the option
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

Default: 1
Range: 0 to 3

F6-02
(3A3)

External Fault
Detection Conditions
(EF0)

Sets the condition for external fault detection (EF0)
0: Always detected
1: Detected only during operation

Default: 0
Range: 0, 1

F6-03
(3A4)

Stopping Method for
External Fault from
Communication
Option

Determines drive response for external fault input (EF0)
detection during CompoNet communication
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

Default: 1
Range: 0 to 3

F6-07
(3A8)

NetRef/ComRef
Selection Function

0: Multi-step speed reference disabled
1: Multi-step speed reference allowed

Default: 1
Range: 0, 1

F6-08
(36A)

Reset
Communication
Related Parameters

Determines which F6-†† and F7-†† parameters are
reset to default values when the drive is initialized using
A1-03.
0: Do not reset parameters
1: Reset parameters

Default: 0
Range: 0, 1

F6-40
(3D5)

<3>

MAC ID

Selects the drive MAC address
Note: Used in the CompoNet Link Object

Default: 0
Min: 0
Max: 63