6 related parameters – Yaskawa AC Drive V1000-Series Option SI-M3/V CompoNet User Manual
Page 30

6 Related Parameters
30
YASKAWA ELECTRIC TOBP C730600 54A V1000 Option CompoNet Installation Manual
<1> To start and stop the drive with the CompoNet master device using serial communications, set b1-02 to 3 or set the
“Net Control” bit in the assemblies or Control Supervisor Object. To control the frequency reference of the drive
via the master device, set b1-01 to 3 or set the “Net Reference” bit in the assemblies or AC/DC object.
<2> Setting F6-01 or F6-03 to 3 will allow the drive to continue to operate after detecting a fault. When allowing the
drive to continue operation after fault detection, be sure to take proper safety measures such as installing an
emergency stop switch.
<3> All MAC addresses must be unique.
<4> Unavailable values will initialize Polled Consuming Assembly (PCA) and Polled Producing Assembly (PPA).