Prior to installing the option, Installing the option, V1000 – Yaskawa SI-EN3/V EtherNet/IP for V1000 Drive User Manual

Page 19

Advertising
background image

5 Installation Procedure

YASKAWA ELECTRIC TOBP C730600 60A V1000 Option EtherNet/IP Installation Manual

19

Prior to Installing the Option

Prior to installing the option, wire the drive, make necessary connections to the drive

terminals, and verify that the drive functions normally without the option installed. Refer to

the Quick Start Guide packaged with the drive for information on wiring and connecting the

drive.

Installing the Option

Refer to the instructions below to install the option.

DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to

comply could result in death or serious injury. Before installing the option, disconnect all power to the drive.

The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED

will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes

after all indicators are off and measure the DC bus voltage level to confirm safe level.

1.

Shut off power to the drive, wait at least five minutes after confirming the DC bus
voltage is safe, then loosen the screw that fastens the front cover in place and

remove the front cover. This drive front cover will be replaced by the option cover.

Cover removal varies depending on drive size.

NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling

the option, drive, and circuit boards. Failure to comply may result in ESD damage to circuitry.

Figure 4

Figure 4 Remove Front Cover

V1000

EtherNet_IM_E_conditional.fm 19 ページ 2012年3月16日 金曜日 午後6時5分

Advertising