11 Troubleshooting
46
YASKAWA ELECTRIC TOBP C730600 60A V1000 Option EtherNet/IP Installation Manual
■
Minor Faults and Alarms
LED Operator Display
Minor Fault Name
CALL
Serial communication transmission error
Communication is not established.
Cause
Possible Solution
Minor Fault
(H2- = 10)
Communication wiring is
faulty, there is a short
circuit, or improper
connection.
Check for wiring errors:
• Correct the wiring
• Remove ground shorts and reconnect loose wires
YES
Programming error on the
master side.
Check communications at start-up and correct programming errors.
Communication circuitry is
damaged.
• Perform a self-diagnostics check
• Replace the drive if the fault continues to occur