11 Troubleshooting

46

YASKAWA ELECTRIC TOBP C730600 60A V1000 Option EtherNet/IP Installation Manual

Minor Faults and Alarms

LED Operator Display

Minor Fault Name

CALL

Serial communication transmission error
Communication is not established.

Cause

Possible Solution

Minor Fault

(H2-†† = 10)

Communication wiring is
faulty, there is a short
circuit, or improper
connection.

Check for wiring errors:

• Correct the wiring
• Remove ground shorts and reconnect loose wires

YES

Programming error on the
master side.

Check communications at start-up and correct programming errors.

Communication circuitry is
damaged.

• Perform a self-diagnostics check
• Replace the drive if the fault continues to occur