9 Input Assemblies (Drive Produces)

9

Input Assemblies (Drive Produces)

Note: The convention in this manual is from the PLC perspective. An “Input Assembly” is outputted

from this node and read by the PLC. This section details “Input Assemblies” that are “Produced”

by this drive.

Basic Speed Control Input - 70 (0x46)

Input

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

70

0

Running 1

(FWD)

Faulted

1

2

Speed Actual (Low Byte)

3

Speed Actual (High Byte)

Parameter

Data

Faulted

Faulted
0: No Faults Occurred
1: Fault Occurred

Running 1 (FWD)

Forward Running
0: Stop or Reverse Running
1: Forward Running

Speed Actual

Actual Drive Speed
Monitors drive output frequency.
Speed actual data: Output frequency x 2

SS

(SS: Speed scale)

Range: 0 to 0xFFFF
For example, when output frequency of 1024 with a speed scale of 2:
Speed actual data = 1024 x 2

2

= 4096 = 0x1000

Unit depends on o1-03.