5 Installation Procedure

22

YASKAWA ELECTRIC TOBP C730600 60A V1000 Option EtherNet/IP Installation Manual

5.

For IP20/Open-Chassis models, go to Step

9.

on page

24

.

6.

For IP20/NEMA Type 1 enclosure models CIMR-V††A††††F, loosen the screw
on the front of the NEMA Type 1 terminal cover and remove it from the drive. Refer

to

Figure 8

for details.

Refer to

Figure 9

for drive models CIMR-V†BA0006F to BA0018F, 2A0010F to

2A0069F, and 4A0001F to 4A0038F, which require removing the plastic terminal

cover prior to removing the NEMA Type 1 terminal cover.

Note: Installing the option on an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection

while maintaining IP20 conformity.

Figure 8

Figure 8 Remove the NEMA Type 1 Terminal Cover

(CIMR-V†BA0001F to BA0003F, 2A0001F to2A0006F)

Figure 9

Figure 9 Remove the Terminal Cover on an IP20/NEMA Type 1 Drive

(Models CIMR-V†BA0006F to BA0018F; 2A0008F to 2A0069F;

4A0001F to 4A0038F)

V1000

V1000