9 Input Assemblies (Drive Produces)

38

YASKAWA ELECTRIC TOBP C730600 60A V1000 Option EtherNet/IP Installation Manual

Extended Speed Control Input - 71 (0x47)

Input

Instance

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

71

0

At Speed

Ref from

Net

Ctrl from

Net

Ready

Running 2

(REV)

Running 1

(FWD)

Warning

Faulted

1

Drive State

2

Speed Actual (Low Byte)

3

Speed Actual (High Byte)

Name

Description

Faulted

Faulted
0: No Faults Occurred
1: Fault Occurred

Warning

Warning
0: No Warning Occurred
1: Warning Occurred

Running 1 (FWD)

Forward Running
0: Stop or Reverse Running
1: Forward Running

Running 2 (REV)

Reverse Running
0: Stop or Forward Running
1: Reverse Running

Ready

Drive Ready
0: Not Ready
1: Ready

Ctrl from Net

Status of Run command from Network
0: Run command is not from network
1: Run command is from network

Ref from Net

Status of Speed reference from Network
0: Speed reference is not from network
1: Speed reference is from network

At Speed

Speed Agree
0: No Speed Agree
1: Speed actual at speed reference

Drive State

Contains the value from the Control Supervisor (Class 0x29) Instance 1 Attribute 6.

Speed Actual

Actual Drive Speed
Monitors drive output frequency.
Speed actual data: Output frequency x 2

SS

(SS: Speed scale)

Range: 0 to 0xFFFF
For example, when output frequency of 1024 with a speed scale of 2:
Speed actual data = 1024 x 2

2

= 4096 = 0x1000

Unit depends on o1-03.

EtherNet_IM_E_conditional.fm 38 ページ 2012年3月16日 金曜日 午後6時5分

Advertising