11 Troubleshooting

YASKAWA ELECTRIC TOBP C730600 60A V1000 Option EtherNet/IP Installation Manual

47

Explicit Message Communications Errors

When there is a problem with a request message sent from the master in explicit

communications, the drive will return one of the following error codes.

Note: Refer to the MEMOBUS/Modbus Data Table in the Technical Manual for a list of monitor data

using the MEMOBUS/Modbus message area.

Error

Code

(hex)

Description

Cause

Possible Solution

08

Service not supported

The service code is incorrect.

Correct the service code.

09

Invalid attribute value

The attribute is incorrect.

Correct the attribute.

0C

Object state conflict

Attempted to change an drive constant
that cannot be changed while the drive
is running.

Stop the drive.

0E

Attribute not settable

Attempted to change a read-only
attribute.

Correct the service code or
attribute setting.

13

Not enough data

The data size is incorrect.

Correct the data size.

14

Attribute not supported

Attempted to execute a service not
defined for the attribute.

Correct the service code or
attribute setting.

15

Too much data

The data size is incorrect.

Correct the data size.

16

Object does not exist

An unsupported object was specified.

Correct the class or instance
setting.

1F

Vendor-specific error

Attempted to change a drive constant
that cannot be changed while the drive
is running.
Attempted to change a drive constant
to a value outside the setting range.

Stop the drive.
Specify a value within the
setting range.

20

Invalid parameter

Attempted to change to a data value
outside the setting range.

Specify a data value within the
setting range.