6 Related Drive Parameters

32

YASKAWA ELECTRIC TOBP C730600 60A V1000 Option EtherNet/IP Installation Manual

F7-13

(3F1)

Address Mode at Startup

Selects how the option address is set.
0: Static
1: BOOTP
2: DHCP

Default: 2
Range: 0 to 2

F7-14

(3F2)

Duplex Mode Selection

Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate
2: Full duplex forced

Default:

<6>

Range: 0 to 2

F7-15

(3F3)

<7>

Communication Speed
Selection

Sets the communication speed
0: 10 Mbps (Available only with drive software
version PRG: 1012 to 1015)
10: 10 Mbps
100: 100 Mbps

Default:

<8>

Range:

<8>

F7-17

(3F5)

EtherNet/IP Speed Scaling
Factor

Sets the scaling factor for the speed monitor in
EtherNet/IP Class ID 2AH Object.

Default: 0
Min.: -15
Max.: 15

F7-18

(3F6)

EtherNet/IP Current Scaling
Factor

Sets the scaling factor for the output current
monitor in EtherNet/IP Class ID 2AH Object.

Default: 0
Min.: -15
Max.: 15

F7-19

(3F7)

EtherNet/IP Torque Scaling
Factor

Sets the scaling factor for the torque monitor in
EtherNet/IP Class ID 2AH Object.

Default: 0
Min.: -15
Max.: 15

F7-20

(3F8)

EtherNet/IP Power Scaling
Factor

Sets the scaling factor for the power monitor in
EtherNet/IP Class ID 2AH Object.

Default: 0
Min.: -15
Max.: 15

F7-21

(3F9)

EtherNet/IP Voltage Scaling
Factor

Sets the scaling factor for the voltage monitor in
EtherNet/IP Class ID 2AH Object.

Default: 0
Min.: -15
Max.: 15

F7-22
(3FA)

EtherNet/IP Time Scaling

Sets the scaling factor for the time monitor in
EtherNet/IP Class ID 2AH Object.

Default: 0
Min.: -15
Max.: 15

F7-23 to

F7-32

(3FB to 404)

Dynamic Output Assembly
Parameters

Parameters used in Output Assembly 116. Each
parameter contains a MEMOBUS/Modbus
address. The value received for Output Assembly
116 will be written to this corresponding
MEMOBUS/Modbus address. A MEMOBUS/
Modbus address value of 0 means that the value
received for Output Assembly 116 will not be
written to any MEMOBUS/Modbus register.

Default: 0

No.

(Addr.

Hex)

Name

Description

Values

EtherNet_IM_E_conditional.fm 32 ページ 2012年3月16日 金曜日 午後6時5分