5 Installation Procedure

YASKAWA ELECTRIC TOBP C730600 60A V1000 Option EtherNet/IP Installation Manual

27

13.

Connect the ground wire at the option ground terminal. Tighten the screw to 0.5 to
0.6 Nxm or (4.4 to 5.3 in lbs) using an M3 Phillips screwdriver.

Figure 17

Figure 17 Connect the Ground Wire to the Option

14.

To connect the option to a network, firmly connect RJ45 8-pin Shielded Twisted Pair
Cat 5e cable(s) into the modular connector port.

Note: Do not connect or disconnect the communication cable while the drive is powered up or while

the drive is in operation. Failure to comply may cause a static discharge, which will cause the

option card to stop working properly. Cycle power on the drive and option card to reestablish

functionality.

Figure 18

Figure 18 Communication Cable Port

Option ground terminal

V1000

V1000