Table 3, The states, Power-up diagnostics – Yaskawa V1000-Series Option SI-EP3/V PROFINET User Manual

Page 12

Advertising
background image

4 Option Components

12

YASKAWA SIEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Technical Manual

Table 3 Option LED States

Power-Up Diagnostics

An LED test is performed each time the drive is powered up. The initial boot sequence may take several seconds. After
the LEDs have completed the diagnostic LED sequence, the option is successfully initialized. The LEDs then assume
operational conditions as shown in

Table 3

.

Table 4 Power-Up Diagnostic LED Sequence

Name

Indication

Operating Status

Remarks

Color

Status

MS
(visible through
drive cover)

OFF

Power supply OFF

Power is not being supplied to the drive.

Green ON

Option

operating

The option is operating normally and
initialization is complete.

Green

Flashing (1)

Diagnostics

Diagnostic data available.

Green

Flashing (2)

Configuration tool

Identified by a configuration tool.

Red ON

Default

MAC

or

fatal error occurred.

Default MAC address has been programmed or
the option has detected an unrecoverable error.

Red

Flashing (1)

Configuration error (non-fatal)

Configuration error.

Red

Flashing (2)

No IP (non-fatal)

No IP address assigned.

Red

Flashing (3)

No station name (non-fatal)

No station name assigned.

Red

Flashing (4)

Init failure (non-fatal)

Failed to initialize module.

Green/Red

Flashing

Option self-test

The option is in self-test mode.

NS
(visible through
drive cover)

OFF

Offline or Power supply OFF

Green ON

Connected

Connection established with I/O controller and
in RUN mode.

Green

Flashing

Connected and stopped

Connection established with I/O controller and
in STOP mode.

Red ON

BUS

fault

Unrecoverable BUS fault.

Red

Flashing (1)

Lost communication

Host communication is temporarily lost.

Red

Flashing (2)

Lost link

No link detected to network.

10/100
(visible at
RJ45 cable ports)

Yellow

OFF

10 Mbps is established

Yellow

ON

100 Mbps is established

LINK/ACT
(visible at
RJ45 cable ports)

Green

OFF

Link is not established

Green

ON

Link is established

Green

Flashing

Link is established and there is network
activity

Sequence

Module Status (MS)

Network Status (NS)

Time (ms)

1

Green

OFF

250

2

Red

OFF

250

3

Green

OFF

-

4

Green

Green

250

5

Green

Red

250

6

Green

OFF

-

Advertising