12 Web Interface

58

YASKAWA SIEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Technical Manual

Network Tab

The Network tab shows the status of the option network traffic and the status of open I/O connections.

Figure 47

Figure 47 Network Tab View

Table 33 Network Monitor Descriptions

Network Monitor

Explanation

Msg Tx OK

Cumulative number of messages transmit successfully from SI-EP3/V.

Msg Rx OK

Cumulative number of messages received successfully to SI-EP3/V.

Current Connections

Current number of open connections.

Control Connection Delta Time

The time between the last two writes to the Control register, MEMOBUS/Modbus address 0001H.

Msg Tx Dropped

Cumulative number of messages dropped due to output network buffer being full and unable to hold the new
message.

Msg Rx Dropped

Cumulative number of messages dropped due to input network buffer being full and unable to hold the new
message.

Collisions

Cumulative number of collisions (half duplex only) reported by the MAC/PHY (Media Access Control/
Physical Connection).

Msg Tx Errors

Cumulative number of transmit underruns and transmit stops reported by the
MAC/PHY.

Msg Rx Errors

Cumulative number of receive overruns, receive stops, and receive error frames reported by the MAC/PHY.

Tx Retry

Cumulative number of transmits in which the 1st attempt was delayed due to busy medium reported by the
MAC/PHY.

Note: Cumulative counters are reset when the power supply is cycled.