Figure 11 – Yaskawa V1000-Series Option SI-EP3/V PROFINET User Manual
Page 18
6 Procedure A
18
YASKAWA SIEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Technical Manual
5.
On IP20/Open-Chassis models, connect the drive side of the ground wire to the drive ground terminal.
Figure 11
Figure 11 Ground Wire Connection on IP20/Open-Chassis
6.
Proceed to STEP
on page
to continue the option installation procedure for IP20/Open-Chassis models.
7.
for IP20/NEMA Type 1 enclosure models CIMR-VAF, loosen the screw on the front of
the NEMA Type 1 terminal cover and remove it from the drive. Refer to
for details.
for drive models CIMR-VBA0006F to BA0018F, 2A0010F to 2A0069F, and 4A0001F to
4A0038F, which require removing the plastic terminal cover prior to removing the NEMA Type 1 terminal cover.
Figure 12
Figure 12 Remove the NEMA Type 1 Terminal Cover
Figure 13
Figure 13 Remove the Terminal Cover on an IP20/NEMA Type 1 Drive
(Models CIMR-VBA0006F to BA0018F; 2A0010F to 2A0069F; 4A0001F to 4A0038F)
Ground terminal
Ground wire
Ground wire
Drive-side
ground terminal
ring lug (size varies):
M3.5 to M6
Ring lug for
Option ground FE
Size: M3