9 Option Drive Parameters

YASKAWA SIEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Technical Manual

33

9

Option Drive Parameters

Before starting network communications, verify proper setting of drive parameters in

Table 10

using the drive digital

operator.

Table 10 Parameter Settings

No.

Name

Description

Default

b1-01

<1>

Frequency Reference Selection

Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse Input (Terminal RP)

1

(Set to 3 for

PROFINET)

b1-02

<1>

Run Command Selection

Selects the run command input source.
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus communications
3: Option PCB

1

(Set to 3 for

PROFINET)

F6-01

Operation Selection after
Communications Error

Determines drive response when a bUS error is detected during
communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

4: Alarm (d1-04)

<5>

5: Alarm Ramp to Stop

<5>

1

F6-02

External Fault Detection Conditions
(EF0)

Sets the condition for external fault detection (EF0).
0: Always detected
1: Detected only during operation

0

F6-03

Stopping Method for External Fault
from Communication Option Board

Determines drive response for external fault input (EF0) detection
during communication.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

1

F6-07

<3>

NetRef/ComRef Selection Function

0: Multi-step speed reference disabled
1: Multi-step speed reference allowed

1

F6-08

<3>

Reset Communication Related
Parameters

Determines if communication-related parameters F6- and F7-
 are set back to original default values when the drive is
initialized using parameter A1-03.
0: Do not reset F6- and F7- parameters
1: Reset F6- and F7- parameters
Note: Setting this parameter does not affect communication-related
parameters.

0

F6-14

<6>

bUS Error Auto Reset

0: Disabled
1: Enabled

0

F7-01 to F7-04

IP Address

Sets static IP address of the SI-EP3/V option when parameter F7-
13=0.
Note: Parameter F7-01 sets the most significant octet.

192 168 1 20

F7-05 to F7-08

Subnet Mask

Sets static Subnet Mask of network connection.
Note: Parameter F7-05 sets the most significant octet

255 255 255 0

F7-09 to F7-12

Gateway Address

Sets static Gateway address of network connection.
Note: Parameter F7-09 sets the most significant octet.

192 168 1 1

F7-13

Address Mode at Startup

Selects how the option address is set.
0: Static
2: DCP

2