YASKAWA SIEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Technical Manual

6 Procedure A

6

Procedure A

Use Procedure A steps to install the option on drives with IP00/IP20 Open Chassis & IP20/NEMA Type 1 enclosures
or enclosure type digits A, B or F within the model number.

Procedure A Steps

DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or

serious injury. Before installing the option, disconnect all power to the drive. The internal capacitor remains charged even after the

power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric

shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level.

NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option, drive, and circuit

boards. Failure to comply may result in ESD damage to circuitry.

1.

Shut off power to the drive, wait at least five minutes after confirming the DC bus voltage is safe, then loosen the
screw that fastens the front cover in place and remove the front cover. This drive front cover will be replaced by
the option cover. Cover removal varies depending on drive size.

Figure 7

Figure 7 Remove the Front Cover

2.

The remaining installation steps differ by drive model. Find the drive model number and identify the Enclosure
Type Digit on the drive nameplate and refer to the appropriate

Table 7

row and “Proceed to STEP” column.

Table 7 Procedure A- Steps by Drive Model

Enclosure Type Digit within

Model Number

Enclosure Type

Drive Model

Proceed to STEP

A, B

IP20/Open-Chassis

CIMR-VAB

3.

on page

17

F

IP20/NEMA Type 1

<1>

<1> Installing the option on an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while maintaining IP20 conformity.

CIMR-VAF

7.

on page

18