2 led and push button description, Table 15 led and push button description, Table 15 – Emerson Liebert Static Transfer Switch User Manual

Page 112: Led and push button description

Advertising
background image

Operating the Liebert STS2 LED Display

104

14.1.2 LED and Push Button Description

The following table defines the LEDs and push buttons in the LED display:

Table 15

LED and push button description

Symbol

LED Description

Action

A

Green

Source 1 power is present

A green LED is lit if the Source 1 input power is present. This LED

only indicates that power is present to the power supply; it does not

indicate if the power is within the programmed tolerances of the unit.

B

Green

Source 2 power is present

A green LED is lit if the Source 2 input power is present. This LED

only indicates that power is present to the power supply; it does not

indicate if the power is within the programmed tolerances of the unit.

C

Green

Source 1 within tolerance

A green LED is lit if Source 1 power is within the programmed

tolerance for all phases.

D

Green

Source 2 within tolerance

A green LED is lit if Source 2 power is within the programmed

tolerance for all phases.

E

Green

Source 1 SCRs on

A green LED is lit when the SCRs for Source 1 are closed.

F

Green

Source 2 SCRs on

A green LED is lit when the SCRs for Source 2 are closed.

G

Yellow

Source transfer inhibited

A yellow (amber) LED is lit when source transfers are inhibited

(locked out) by a hardware condition. Connect a PC terminal to the

Liebert STS2 to locate the exact cause. See 12.0 - Communication

Interfaces for PC terminal commands.

H Green

Push button to select Source 1

as the preferred source

A green LED is lit if the button has been pushed to set Source 1 as

the preferred source.

I Green

Push button to select Source 2

as the preferred source

A green LED is lit if the button has been pushed to set Source 2 as

the preferred source.

J

Green

Output power is present

A green LED is lit to indicate that power is present on the output

load.

K

Alarm silence button

Push this button to turn off the horn that is sounded for an alarm.

This button does not reset an alarm condition, unless pushed

simultaneously with “M” button.

L

Symbol to indicate the K and M

must be pushed at the same

time to reset alarm

M

Alarm reset push button

Push this button simultaneously with the “K” button to reset an alarm

condition. An alarm can only be reset if the hardware condition

permits a reset.

N

Red

Alarm present

A red LED is lit when an alarm condition is present in the Liebert

STS2.

Connect a PC terminal to the Liebert STS2 to locate the exact

cause. See 12.0 - Communication Interfaces for PC terminal

commands.

1

Green

CB1 closed

A green LED is lit if CB1 is closed, indicating power is flowing to the

static transfer switch from Source 1.

2

Green

CB2 closed

A green LED is lit if CB2 is closed, indicating power is flowing to the

static transfer switch from Source 2.

3

Green

CB3 closed

A green LED is lit if the output breaker/switch is closed.

3A

Green

CB3A closed

A green LED is lit if the output breaker/switch is closed. CB3A is

installed on units with dual output breakers.

4

Yellow

CB4 closed

A yellow LED is lit if the Source 1 bypass breaker/switch is closed.

5

Yellow

CB5 closed

A yellow LED is lit if the Source 2 bypass breaker/switch is closed.