Output breaker, Front view, One-line diagram – Emerson Liebert Static Transfer Switch User Manual

Page 39

Advertising
background image

Installation Drawings

31

Figure 18 Electrical field connections drawing: 800 – 1000 amp Liebert STS2 with single output breaker

SECTION A-A

SIDE VIEW

(WITH FRONT PANELS REMOVED)

FRONT VIEW

FRONT VIEW

GROUND BUS

.51 DIA.

NEUTRAL BUS

RIGHT SIDE VIEW

.51 DIA.

INPUT/OUTPUT BUS

RIGHT SIDE VIEW

NEUTRAL

BUS

GROUND

BUS

Ø A, Ø B, Ø

C

SYSTEM OUTPUT

Ø A, Ø B, Ø C

SOURCE 1 INPUT

CB5

CB3

CB2

CB1

CB4

SOURCE 1

INPUT Ø

A

SOURCE 2 INPUT

Ø A, Ø B, Ø C

SOURCE 1

INPUT Ø

B

SOURCE 1

INPUT Ø C

PEM NUT

FRONT

BUS

NEUTRAL

CB3

SYSTEM OUTPUT

ONE-LINE DIAGRAM

PS212800

Rev. 2

CB4

K3

K2

K1

CB5

K3

K1

K2

SOURCE 1

CB1

SOURCE 2

CB2

NOT

RECOMMENDED.

NOTES:

1. ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS).

5. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL

4.

ALUMINUM

AND

COPPER

CLAD ALUMINUM CABLES ARE

3. CONTROL WIRING AND POWER WIRING MUST BE RUN

2. TOP AND BOTTOM CABLE ENTRY AVAILABLE THROUGH

AND LOCAL ELECTRICAL CODES.

RUN IN A SEPARATE CONDUIT FROM INPUT CABLES.

IN SEPARATE CONDUIT. OUTPUT CABLES SHOULD BE

CONDUIT SIZE, AND REPLACE.

REMOVABLE ACCESS PLATES. REMOVE, PUNCH TO SUIT

NEUTRAL, AND GROUND CABLE CONNECTIONS. KIT

6. HARDWARE KIT IS SUPPLIED FOR INPUT, OUTPUT,

INCLUDES 1/2" BOLTS, WASHERS, AND NUTS FOR CONNECTING

CABLES TO THE BUS BARS.

7. THE TORQUE REQUIREMENT FOR 1/2"-13 PEM NUTS IS

428 INCH-LBS. (48 N-m).