Emerson Liebert Static Transfer Switch User Manual

Page 88

Advertising
background image

Communication Interfaces

80

Group 3:

User

Settings

1

SCR1 Fast Undervoltage

Setpoint

Integer

In % of nominal below nominal

2

SCR1 Slow Undervoltage

Setpoint

Integer

In % of nominal below nominal

3

SCR1 Slow Undervoltage

Detect Delay

Integer

In number of lines cycles

4

SCR1 Overvoltage

Setpoint

Integer

In % of nominal above nominal

5

SCR1 Overvoltage Detect

Delay

Integer

In 1/4 lines cycles

6

SCR1 I peak Transfer

Setpoint

Integer

x 10

7

SCR2 Fast Undervoltage

Setpoint

Integer

In % of nominal below nominal

8

SCR2 Slow Undervoltage

Setpoint

Integer

In % of nominal below nominal

9

SCR2 Slow Undervoltage

Detect Delay

Integer

In number of lines cycles

10

SCR2 Overvoltage

Setpoint

Integer

In % of nominal above nominal

11

SCR2 Overvoltage Detect

Delay

Integer

In 1/4 lines cycles

12

SCR2 I peak Transfer

Setpoint

Integer

x 10

13

Max. Transfer Phase

Angle

Integer

In degrees

14

Output Frequency

Deviation

Integer

Freq. in Hz x 10

15

ReTransfer Delay Time

Integer

In seconds

16

Horn Volume

Integer

Range: 1-10

17

Critical Option Enabling

Bitpacked

See section 12.1.3.

18

Non-Critical Option

Enabling

Bitpacked

See section 12.1.3.

Group 4:

Event Mask

Settings

1 to

63

Event Mask settings for

faults

Event Mask

See section 12.1.4.

64 to

143

Event Mask settings for

alarms

Event Mask

See section 12.1.4.

Table 11

Group settings and values (continued)

Group

Item:

Description

Value Type

Value Notes

Advertising