Installation Drawings

33

Figure 20 Liebert STS2 non-automatic circuit breaker schedule

Liebert STS2

Ampere

Rating, A

Vendor

Type

Ampacity, A

Voltage

Withstand

Current

100

Square D

HL

150

200-240V

380-480V

600V

125K

100K

50K

250

Square D

JL

250

200-240V

380-480V

600V

125K

100K

50K

400

Merlin Gerin

NSJ

400

200-240V

380-480V

600V

100K

100K

25K

600

Merlin Gerin

NSJ

600

200-240V

380-480V

600V

100K

100K

25K

800

Square D

PJ

800

200-240V

380-480V

600V

100K

65K

25K

1000

Square D

PJ

1200

200-240V

380-480V

600V

100K

65K

25K

1. The Liebert STS2 non-automatic breakers are 3-pole, 600VAC rated with magnetic trip only.
2. Upstream devices (by others) must be used to provide overcurrent protection. Upstream overcurrent protection should

have ampacity equal to or less than the ampere rating of the static switch.