Figure 29 outline drawing for input junction box, Figure 29, Input junction box – Emerson Liebert Static Transfer Switch User Manual

Page 50

Advertising
background image

Installation Drawings

42

Figure 29 Outline drawing for input junction box

G

C

B

A

B

D

E

H

G
Diameter hole

A

C

INPUT JUNCTION BOX

Location of

Factory-Supplied

Input Power

Cable Assembly

Recommended Location for

Customer Connection of Input

Power Raceway (by others)

3-Phase, 3-Wire Plus Ground

Power Terminal Block

PS211005
Rev. 0

NOTES:

1. Two junction boxes are supplied, one for each input.

2. Cable(s) are factory-supplied to connect the junction

box to the input busbars. See electrical field

connections drawing for location.

3. Parallel cables are used on 400A and 600A units.

Input Junction Box

Rating

Dimensional Data - Inches (mm)

Wire Size Range

A

B

C

D

E

F

G

H

100A

16 (406) 14 (356) 6 (152) 17-1/2 (445) 12 (305) 16-3/4 (426) 5/16 (8) 1 (25) #6 AWG to #2/0 AWG

250A - 600A 16 (406) 30 (762) 6 (152)

33 (830)

10 (254)

32 (813)

7/16 (11) 3 (76)

(2) #6 AWG to (2)

500 kcmil