Table 8 event messages, Table 8, Event messages – Emerson Liebert Static Transfer Switch User Manual

Page 82

Advertising
background image

Alarm and Faults

74

.

Table 8

Event messages

ID

Alarm Message

Description/Cause

Action

001

S1 SCR SHORT

One or more of the SCRs for Source 1 have shorted and failed.

D, F, A, E

002

S2 SCR SHORT

One or more of the SCRs for Source 2 have shorted and failed.

D, F, A, E

003

S1 SCR OPEN

One or more of the SCRs for Source 1 is open.

D, F, A, E

004

S2 SCR OPEN

One or more of the SCRs for Source 2 is open.

D, F, A, E

005

PRIMARY FAN FAIL

A primary cooling fan has failed and the unit is now being

cooled by a secondary fan, which is not monitored.

D, A, E

006

CONTROL MODULE FAIL

Control logic module has failed.

D, A, E

007

PWR SPLY DC A FAIL

Power supply DC bus A has failed.

D, A, E

008

PWR SPLY DC B FAIL

Power supply DC bus B has failed.

D, A, E

009

PWR SPLY S1 AC FAIL

Power supply Source 1 AC has failed.

D, A, E

010

PWR SPLY S2 AC FAIL

Power supply Source 2 AC has failed.

D, A, E

011

PWR SPLY LOGIC FAIL

A power supply module has failed.

D, A, E

012

OUT VOLT SENSE FAIL

The output volt sense module failed

D, A, E

013

S1 VOLT SENSE FAIL

The Source 1 volt sense module failed.

D, A, E

014

S2 VOLT SENSE FAIL

The Source 2 volt sense module failed.

D, A, E

015

S1 SCR SENSE FAIL

The Source 1 SCR sense module failed.

D, A, E

016

S2 SCR SENSE FAIL

The Source 2 SCR sense module failed.

D, A, E

017

S1 CURR SENSE FAIL

The Source 1 SCR current module failed.

D, A, E

018

S2 CURR SENSE FAIL

The Source 2 SCR current module failed.

D, A, E

019

S1 GATE DRIVE FAIL

The Source 1 gate drive module failed.

D, A, E

020

S2 GATE DRIVE FAIL

The Source 2 gate drive module failed.

D, A, E

021

INTERNAL COMM FAIL

Internal CAN communications failed.

D, A, E

022

EXTERNAL COMM FAIL

Options CAN communications failed.

A, E

023

CB1 SHUNT TRIP FAIL

CB1 shunt trip failed.

A, E

024

CB2 SHUNT TRIP FAIL

CB2 shunt trip failed.

D, A, E

064

HEATSINK OVERTEMP

Heatsink has exceeded the recommended temperature.

A, E

067

S1 UV

Source 1 under voltage, fast detection.

A, E

068

S1 UV (RMS)

Source 1 under voltage, slow detection.

L, A, E

069

S1 OV

Source 1 over voltage

A, E

070

S1 OF/UF

Source 1 over frequency/under frequency

A, E

071

S1 FAIL

Source 1 failure.

A, E

072

S2 UV

Source 2 under voltage, fast detection.

A, E

073

S2 UV (RMS)

Source 2 under voltage, slow detection.

A, E

074

S2 OV

Source 2 over voltage.

A, E

075

S2 OF/UF

Source 2 over frequency/under frequency.

A, E

076

S2 FAIL

Source 2 failure.

A, E

077

S1 OVERCURRENT

Source 1 over current.

A, E

078

S2 OVERCURRENT

Source 2 over current.

A, E

079

S1 I-PEAK

I-PK on Source 1.

A, F, E

080

S2 I-PEAK

I-PK on Source 2.

A, F, E

081

SOURCES OUT OF SYNC

Source 1 and Source 2 are out of synchronization.

A, E

082

LOAD ON ALT SOURCE

The output load is running on the alternate source.

A, E

083

AUTO REXFER INHIBIT

Automatic retransfer is inhibited.

A, E