Figure 25 – Emerson Liebert Static Transfer Switch User Manual

Page 46

Advertising
background image

Installation Drawings

38

Figure 25 Control wiring for the input contact isolator board option

1

16

2 3 4 5

7 8 9

6

15

14

13

12

11

10

J51

“NO CUSTOMER CONNECTION”

INPUT CONTACT ISOLATOR BOARD

02-810012-XX

PS213002
Rev. 02

NOTES:

1. Customer control wiring connection points are Terminals 1 through 16

(see Table J51).

2. Customer-provided, normally open, dry contacts for user alarm messages.

3. Refer to installation, operation AND maintenance manual for configuring the

input contact isolator board option.

4. All control wiring (by others) must be run separate from power wiring. Control

wiring runs should not be combined in the same conduit.

5. Refer to static transfer switch control connection diagram for location of input

contact isolator board option.

6. Signal voltage: 100mA @ 12VDC.

7. Maximum cable length 500 ft. (152 meters) with #16 AWG flexible, stranded cable.

8. All wiring must be in accordance with national and local electrical codes.

Table J51

Input

Contact

Pin No.

1

1
2

2

3
4

3

5
6

4

7
8

5

9

10

6

11
12

7

13
14

8

15
16