Figure 23, Figure 23 for – Emerson Liebert Static Transfer Switch User Manual

Page 44

Advertising
background image

Installation Drawings

36

Figure 23 Control wiring for remote source selection option

1

2

3

4

6

5

See Note 1

S2

S1 GND

GND

Remote Source Selection

PS213007
Rev. 02

NOTES
1. Customer-provided normally open dry contacts. Rating 10mA at 30VDC.
2. Maximum cable length 500 ft. (152m) with #16 AWG, 300V minimum

flexible stranded cable.

3. All control wiring (by others) must be run separate from power wiring .

Control wiring runs should not be combined in the same conduit.

4. Refer to Static Transfer Switch control diagram for location of remote source

selection opt.

5. All wiring must be in accordance with national and local electrical codes.

TB50

Source 1

Preferred

Source 2

Preferred

Advertising