System seismic anchoring, figure 1, Front – Emerson Liebert Static Transfer Switch User Manual

Page 34

Advertising
background image

Installation Drawings

26

Figure 13 Seismic anchor drawing: 800 – 1000 amp Liebert STS2

5.

MOVE

CABINET

INTO

P

OSITION

W

ITH

REAR

TABS

INTO

S

LOTS

OF

FLOOR BRACKET. TABS TO EXTEND AT LEAST 1/2" THROUGH FLOOR

BRACKET

(FIG.

2).

THEN

ATTACH

FRONT FLOOR BRACKETS

TO

FRONT

CABINET

BASE

BRACKET

BUT

DO

N

OT

FULLY

T

IGHTEN

HARDWARE.

6.

MARK

HOLE LOCATIONS AND REMOVE BRACKETS. DRILL AND INSTALL

FLOOR

BRACKETS.

UNIT

DOOR

CAN BE

REMOVED

FOR BETTER

ACCESS.

REINSTALL

FRONT FLOOR BRACKETS

TO

FRONT CABINET

BRACKETS

WITH

SUPPLIED HARDWARE AND TORQUE TO 235 LB-IN (26.5 Nm), (FIG. 3).

7.

IF

SIDE

WALLS

ARE

PRESENT,

5.0

INCH

MINIMUM

D

ISTANCE

FROM

EITHER

SIDE WALL

IS

REQUIRED.

8. REAR

A

ND

FRONT

FLOOR

BRACKETS,

AND

REAR

AND

FRONT

CABINE

T

BASE BRACKETS

ARE

1010

STEEL

AND

APPROX.

.25

INCH

THICK.

NOTES:

1. RECOMMENDED

FLOOR

ANCHOR:

1/2"

ITW

RAMSET/RED

HEAD

SELF DRILLING

ANCHOR,

ICBO

#ER-1372

OR

EQUIVALENT

(NOT

(SUPPLIED). FOLLOW MANUFACTURER'S INSTRUCTIONS.

2. POSITION

REAR

FLOOR

BRACKETS

ON

FLOOR

AT

LEAST

.75"

FROM

BACK WALL.

MARK

LOCATION

A

ND

DRILL

HOLES

(FIG.

1)

TO

A MINIMUM DEPTH OF 4.12" INTO THE CONCRETE.

3. INSTALL

REAR

CABINET

BASE

BRACKET

(FIG.

2)

TO

EXISTING

HOLES ON UNDERSIDE OF UNIT WITH TABS FACING BACK WALL.

USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm). NOTE, LOOSEN

LEVELING

BOLT

LOCKING

NUT

AND

TIGHTEN

AFTER

BRACKET IS

SECURED.

4. INSTALL

FRONT

CABINET

BASE

BRACKET

(FIG.

3)

TO

EXISTING

HOLES

ON

U

NDERSIDE

OF

UNIT WITH BENT FLANGE FACING FRONT.

USE SUPPLIED HARDWARE AND TORQUE TO 365 LB-INCH (41.2 Nm).

NOTE, LOOSEN

LEVELING

BOLT

LOCKING

NUT

AND

TIGHTEN

AFTER

BRACKET IS

SECURED.

SYSTEM SEISMIC ANCHORING,

FIGURE

1

TOP VIEW

32.

2"

(817

MM)

FRONT

13

.2"

(335 MM)

13

.2"

15

.6"

(335 MM)

(39

6 M

M)

(310

M

M)

12

.2"

13

.2"

(335 MM

)

13

.2"

(335 MM)

(107

MM) 4.2"

(107

MM) 4.2"

11.4

"

(289 M

M)

(107

M

M)

4.2"

4.2"

(107

M

M)

(144 M

M)

5.7

"

32.

75

"

(832 MM)

SEE NOTE

(7)

FOR SPACING

BACK WALL

REAR FLOOR BRACKET SEE NOTE

(2)

FOR SPACING

FRONT FLOOR BRACKET

SIDE WALL

PS211805 Rev. 0

FLOOR ANCHOR HARDWARE (NOT SUPPLIED

)

FIGURE 2

REAR CABINET BASE BRACKET

FLOOR LINE

BRACKET

REAR F

LOOR

APPROX 1/2"

BACK WALL

FRONT CABINET BASE BRACKET

FIGURE 3

BRACKET

FLOOR ANCHOR HARDWARE NOT SUPPLIED

FRONT FLOOR

FRONT DOOR OF CABINET

HARDWARE SUPPLIED

FLOOR LINE