11 rs-232 interface parameters, Table 23 rs-232 settings, 12 maintenance bypass – Emerson Liebert Static Transfer Switch User Manual

Page 124: 13 fuseless design, 14 options, Table 23, Rs-232 settings

Advertising
background image

Specifications

116

15.2.11 RS-232 Interface Parameters

The service terminal interface parameters are the following settings and cannot be changed.

15.2.12 Maintenance Bypass

The Liebert STS2 is configured to allow the unit’s electronics to be bypassed to either input source for

maintenance without interruption of power to the load.
The Liebert STS2 is furnished with key-interlocked maintenance bypass breakers to configure the

bypass.
Liebert STS2 units have all electronics isolated from the input, output, and bypass connections to

allow safe servicing of any components without access to hazardous voltages when the unit is in main-

tenance bypass.
See 10.4 - Maintenance Bypass on page 67 for instructions using the Color LCD Graphical Display

unit and 14.2.3 - Maintenance Bypass on page 108 for instructions using the LED units.

15.2.13 Fuseless Design

All Liebert STS2 units are fuseless and are UL rated for use with upstream circuit breakers only.

15.2.14 Options

The following options are available for the Liebert STS2:

See 6.0 - Options for more information.

Table 23

RS-232 settings

Parameter Setting

Interface

RS-232 Using EIA Voltage Levels

Baud Rate

9600

Parity None
Number of Data Bits

8

Number of Stop Bits

1

Hardware Flow Control

Off

Terminator <CR>

<LF>

Handshaking Not

supported

Structure Full

duplex

Local Echo

Off

Optimized Transfer

LED Display

Redundant Output Breaker

Liebert IS-WEB485ADPT

Distribution Cabinet With I-Line Panelboard

Seismic Floor Stand - 18", 24", 30" and 36"

Input Junction Boxes and Cable

Export Crating

Comms Board w/Liebert SiteScan and Modem Interface

Remote Source Selection

Input Contact Isolator Board

Key Lockout Switch

Programmable Relay Board

Advertising