Table 3

Input junction box dimensions

Switch Rating

Length

Inches (mm)

Width

Inches (mm)

Height

Inches (mm)

100 amp

16 (406)

14 (356)

6 (152)

250 to 600 amp

30 (762)

16 (406)

6 (152)

Table 4

Input junction box terminal wire size range

Switch Rating

Power and Ground Lug Wire Range

100 amp

#6 to #2/0 AWG

250 to 600 amp

(2) #6 AWG to (2) 500 kcmil