Table 2 input/output conduit plate specifications, 2 input junction box installation—optional, Input junction box installation—optional – Emerson Liebert Static Transfer Switch User Manual

Page 18: Figure 3, Typical static transfer switch one-line diagram, Table 2, Input/output conduit plate specifications, 2 - input junction box

Advertising
background image

Power and Control Wiring

10

Figure 3

Typical static transfer switch one-line diagram

The input and output power wire size should be based on the upstream overcurrent protection device,

observing the NEC and local codes.
The molded case switches contained in the Liebert STS2 are typically non-automatic circuit breakers

that rely on the upstream and/or load overcurrent protection. Upstream overcurrent protection

should be rated equal to or less than the rating of the Liebert STS2 molded case switches.
The Liebert STS2 input and output power and ground and neutral bus bars accommodate a wide

range of wire sizes. The Liebert STS2 bus bars accommodates standard 2 hole lugs.

5.2

Input Junction Box Installation—Optional

The input junction box option is available to simplify input connections to the Liebert STS2. Two

input junction boxes and the associated flexible 10 foot long (3 meter) input cables are provided with

this option.
This option is available only with bottom cable entrance, typically when the unit is located on a raised

floor.
If the input junction boxes will be used, they may be shipped either with the unit or in advance to be

installed during the rough-in stage of construction.
Locate the junction boxes a maximum of 8 feet (2.4 meters) from the planned location of the Liebert

Static Transfer Switch.
Due to a lack of clearance for the cables below the unit, the cables are also shipped loose from the unit

for installation at the site. The input cables connect from the input junction boxes to the input power

bus bars inside the Liebert STS2.
The standard configuration for the input junction boxes and cables is for 3-wire-plus-ground feeds. If

the input neutral is required, special 4-wire-plus-ground input cables and junction boxes are required.

See Figure 29 for wiring details.

Table 2

Input/output conduit plate specifications

Rating

Max. number and size

100-250A

6 — 3" conduit

400-600A

9 — 4" conduit

800-1000A

12 — 4" conduits

K2

K1

K1 K3

K2 K3

CB4

CB5

CB2

CB3

STS2

STS1

OUTPUT

CB1

SOURCE 1

SOURCE 2