Figure 53 user settings dialog box, Source set points – Emerson Liebert Static Transfer Switch User Manual

Page 98

Advertising
background image

Liebert STS2 Touch Screen Display

90

Figure 53 User settings dialog box

Source Set Points

The Source 1/2 Set Points allows you to configure trigger points for each input source (1 or 2) for the

Liebert STS2 via a keypad dialog or HI/LO dialog box. The source numbers do not designate the

source as the preferred or alternate source. The numbers simply identify the input source. See 10.2 -

Manual Transfer / Preferred Source Selection to set the preferred source.
The Set Points are based on values in relation to the nominal voltage required for the Liebert STS2.

UV refers to under voltage, meaning the amount of voltage below the nominal voltage. OV refers to

over voltage, or the amount of voltage over the nominal voltage.

Fast UV Setting (%)if the voltage drops below this set percentage of the nominal voltage, the

Liebert STS2 transfers from the current source to the opposite source.

Slow UV Setting (%)if the voltage remains this set percentage below the nominal voltage for

the period of the slow detection delay, the Liebert STS2 transfers from the current source to the

opposite source.

Slow UV detection delaythe number of cycles that the source must remain below the Slow UV

Setting before the Liebert STS2 transfers.

OV Setting (%)if the voltage exceeds this set percentage of the nominal voltage for the period of

the OV detection delay, the Liebert STS2 transfers from the current source to the opposite source.

OV Detection Delaythe number of cycles that the source must remain above the OV Setting

before the Liebert STS2 transfers sources.

I-PK Xfer Lockoutif current from the source exceeds this threshold, the Liebert STS2 disables

source transfers, and has to be reset either manually or automatically. The type of reset is config-

ured under the User Settings.