Installation Drawings

40

Figure 27 Control wiring for the Liebert IntelliSlot Web/485 Card with Adapater

+

-

1

23

TB

3

Notes:

1. Wire size and type: 10/100 base-T

ethernet

cable with RJ-45 plug connector

.

The length is

limited by internet standards.

2. Maximum cable length 1000 feet (300 meters)

with twisted pair cable #22

A

W

G minimum. Signal

voltage 5VDC, current 10mA.

3. Refer to the Liebert Intellislot W

eb/485 Card’

s

installation, operation & maintenance manual for

configuration details.

4.

All control wiring (by others) must be run

separate from power wiring. Control wiring runs

should not be combined in the same conduit.

5. Refer to control connection location diagram

of static transfer switch for location of Liebert

Intellislot W

eb/485 card option.

6.

All wiring must be in accordance with national

and local electrical codes.

Customer-supplied

interconnection cable

to Modbus

See Note 2

No customer

connection

No customer

connection

RS-232 (DB-9 connector)

for setup only

. Uses standard

computer serial port cable

Ethernet Network

RF-45 Connector

See Notes 1 and 2

Customer-Supplied

Interconnection Cable

TB3

TB2

TB1

DB-9

J3

PS213008

Rev

. 01