Amprobe GP-2 Geo-Test User Manual

Page 18

Advertising
background image

GP-2 GeoTest

EN - 18

Press SAVE to store the test results in memory (see paragraph 5.1).

Example:

You position the rods at a distance D of 3 feet and take 3 resistivity measurements:

7.7

7.7

m

ρρ

7.1

7.1

m

ρρ

A

A

dd

7.1

7.1

m

ρρ

A

A

dd

1

st

meas.

2

nd

meas.

3

rd

meas.

a) 1

st

measurement: you see the measured value but not the message “Add”.

b) 2

nd

measurement: you see the message “Add”. This means that the second

measurement is included in the calculation of the average; by pressing AVG you will
get also the average value calculated.

7.4

7.4

m

ρρ

002 A

002 A

dd

The "002" indicates that 7.4

m is the average value calculated as the average

between the two values previously measured.
Press ESC to return back to the screen corresponding to the second measurement.
Upon returning back to the second measurement, press CLR if you want to cancel the
average value calculated and the corresponding counter.

c)

3

rd

measurement: as with point b) above, but the average value is calculated as

average between the three values measured.

7.3

7.3

m

ρρ

003 A

003 A

dd

The "003" indicates that 7.3

m is the average value calculated as average between

the three values previously measured.

SAVE

This screen appears
after press in AVG

This screen appears
after pressing AVG