Appendix B:

Recommended Use of the

Connection Wires

(Applicable to the system with voltage attenuation less than 3%) The following table is applicable
to the applications in the system.

Distance in feet ( meters )

Amps

24 AWG

22 AWG

20 AWG

18 AWG

16 AWG

14 AWG

2.5

5.6 ft

(1.95m)

8.8 ft

(2.70m)

14.12 ft

(4.30m)

22.50 ft

(6.86 m)

36.0 ft

(11.0m)

56.4 ft

(17.22m)

5.0

2.80 ft

(0.86m)

4.4 ft

(1.36m)

7.06 ft

(2.16m)

11.26 ft

(3.42m)

18.0 ft

(5.48m)

28.2 ft

(8.6m)

7.5

1.86 ft

(0.56m)

2.96 ft

(0.90m)

4.70 ft

(1.44m)

7.50 ft

(2.28m)

12.0 ft

(3.66m)

18.82 ft

(5.74m)

10

1.40 ft

(0.42m)

2.22ft

(0.68m)

3.52 ft

(1.08m)

5.62 ft

(1.72m)

9.0 ft

(2.74m)

14.12 ft

(4.30m)

12.5

1.12 ft

(0.34m)

1.78ft

(0.54m)

2.82 ft

(0.86m)

4.50 ft

(1.38m)

7.20 ft

(2.20m)

11.30 ft

(3.44m)

15

0.94 ft

(0.28m)

1.48 ft

(0.46m)

2.36 ft

(0.72m)

3.76 ft

(1.14m)

6.0 ft

(1.82m)

9.42 ft

(2.86m)

 

 

 

 
 