LED Status Indicators

The LEDs indicate the module's operating status as follows:

Module Color

Status

Indication

On

Data is being transferred between the module and a remote
terminal using the Configuration/Debug port.

CFG Green

Off

No data is being transferred on the Configuration/Debug port.

Off

The MVI69-EGD is working normally.

APP STATUS Amber

On

The MVI69-EGD module program has recognized a
communication error on one of its ports.

On

The LED is on when the module is performing a write operation
on the backplane.

BP ACT

Amber

Off

The LED is off when the module is performing a read operation
on the backplane. Under normal operation, the LED should
blink rapidly on and off.

Off

The card is not receiving any power and is not securely
plugged into the rack.

Green

The module is operating normally.

OK

Red/
Green

Red

The program has detected an error or is being configured. If
the LED remains red for over 10 seconds, the program has
probably halted. Remove the card from the rack and re-insert
the card to restart the module's program.

Off

The battery voltage is OK and functioning.

BATT Red

On

The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If BAT LED still does not go off, contact ProSoft
Technology, as this is not a user serviceable item.

If the APP, BP ACT and OK LEDs blink at a rate of every one-second, call
ProSoft Technology support. There is a serious problem with the module, and it
will have to be sent back to ProSoft.

4.2.1 Ethernet LED Indicators

LED State

Description

Off

No activity on the port.

Data

Green Flash

The port is either actively transmitting or receiving data.

Off

No connection to hub or network is detected.

Link

Green Solid

Connected to hub or network correctly. This is the normal
operating state.

Advertising