Reference MVI69-EGD

♦ CompactLogix or MicroLogix Platform

GE Ethernet Global Data Communication Module

ProSoft Technology, Inc.

Page 67 of 96

November 3, 2008

Packet
Info

Description Data

Reserved:

12

4

0x HH HH HH HH

Maximum Exchanges:

16

4

0x HH HH HH HH

Capabilities Bit Mask:

20

4

0x HH HH HH HH

Reserved:

24

2

0x HH HH

Configuration Type:

26

2

0x HH HH

Identification String

(up to 80 characters):

28

XX

0x HH . . . HH

Summary PDUs

PDU Type = 7

Summary Request

The summary request PDU command permits an application program to request
a summary of the exchanges configured on a given node. This allows a user to
get a complete list of all exchanges defined. The Index field is normally 0 and is
used to request a block of summaries in nodes which contain a large number of
exchanges. A summary request sent from a requesting node must be followed by
a summary response message from the responding node.

Packet
Info

Description Data

Source Port:

7937 (0x 1F01)

Destination Port:

7937 (0x 1F01)

Length:

xx bytes (0x 00 XX)

Checksum:

xxxxx (0x XX XX)

EGD's PDU Field:

Offset

Bytes

Hex code

PDU Type:

0

1

0x 07

Message Flag:

1

1

0x HH

Request ID:

2

2

0x HH HH

PVN1:

4

1

0x 01

Reserved:

5

1

0x HH

Message Length:

6

2

0x HH HH

Index:

8

1

0x HH

UDP

EGD:

Reserved:

9

3

0x 00 00 00