E 69) – ProSoft Technology MVI69-EGD User Manual

Page 69

Advertising
background image

Reference MVI69-EGD

♦ CompactLogix or MicroLogix Platform

GE Ethernet Global Data Communication Module

ProSoft Technology, Inc.

Page 69 of 96

November 3, 2008

Statistics PDUs

PDU Type = 15

Statistics Request

The statistics request PDU command permits an application program to obtain
the current operating statistics of the specified Exchange. The exchange must be
valid on the destination node. A statistics request sent from a requesting node
must be followed by a statistics response message from the responding node.

Packet
Info

Description Data

Source Port:

7937 (0x 1F01)

Destination Port:

7937 (0x 1F01)

Length:

xx bytes (0x 00 XX)

Checksum:

xxxxx (0x XX XX)

EGD's PDU Field:

Offset

Bytes

Hex code

PDU Type:

0

1

0x 0F

Message Flag:

1

1

0x HH

Request ID:

2

2

0x HH HH

PVN1:

4

1

0x 01

Reserved:

5

1

0x HH

Message Length:

6

2

0x HH HH

Producer ID:

8

4

0x HH HH HH HH

UDP

EGD:

Exchange ID:

12

4

0x HH HH HH HH

PDU Type = 16

Statistics Response.

The statistics response PDU command returns the operating statistics for the
Producer and Exchange ID specified in the request message.

Packet
Info

Description Data

Source Port:

7937 (0x 1F01)

Destination Port:

7937 (0x 1F01)

Length:

xx bytes (0x 00 XX)

Checksum:

xxxxx (0x XX XX)

EGD's PDU Field:

Offset

Bytes

Hex code

PDU Type:

0

1

0x 10

Message Flag:

1

1

0x HH

Request ID:

2

2

0x HH HH

PVN1:

4

1

0x 01

Status:

5

1

0x HH

Message Length:

6

2

0x HH HH

Producer ID:

8

4

0x HH HH HH HH

Exchange ID:

12

4

0x HH HH HH HH

Configuration Time:

16

4

0x HH HH HH HH

UDP

EGD:

Due Time:

20

4

0x HH HH HH HH

Advertising
This manual is related to the following products: