Packet
Info

Description Data

State:

24

4

0x HH HH HH HH

Exchange Length:

28

4

0x HH HH HH HH

Message Count:

32

4

0x HH HH HH HH

Missed Count:

36

4

0x HH HH HH HH

Refresh Error Count:

40

4

0x HH HH HH HH

Reserved:

44

4

0x HH HH HH HH

Command NAK PDU

PDU Type = 18

Command NAK Response.

The command NAK response may be sent by a responder to any command
received on the command port that is in error. Use of the command NAK allows
the responder to give more precise and detailed information about the nature of
the error to the requester. The command NAK shall not be sent in response to a
NAK message.

The NAK message is returned to indicate a syntactic error in a request message.
It should only be used if the request is unintelligible. Thus, whenever possible,
the corresponding response to a received request message shall be returned.

Packet
Info

Description Data

Source Port:

7937 (0x 1F01)

Destination Port:

7937 (0x 1F01)

Length:

xx bytes (0x 00 XX)

Checksum:

xxxxx (0x XX XX)

EGD's PDU Field:

Offset

Bytes

Hex code

PDU Type:

0

1

0x 12

Message Flag:

1

1

0x HH

Request ID:

2

2

0x HH HH

PVN1:

4

1

0x 01

Status:

5

1

0x HH

Message Length:

6

2

0x HH HH

Producer ID:

8

4

0x HH HH HH HH

Exchange ID:

12

4

0x HH HH HH HH

UDP

EGD:

Error Code:

16

2

0x HH HH

Reserved:

18

2

0x HH HH

Offending
Message:

20

16

0x HH . . . HH

Error String:

(up to 80
characters)

36

XX

0x HH . . . HH