Reference MVI69-EGD

♦ CompactLogix or MicroLogix Platform

GE Ethernet Global Data Communication Module

ProSoft Technology, Inc.

Page 65 of 96

November 3, 2008

Request ID:

2

2

0x 11 11

PVN1:

4

1

0x 01

Status:

5

1

0x 00

Message
Length:

6

2

0x 4C 00

Producer ID:

8

4

0x 69 66 00 C8

Exchange ID:

12

4

0x E1 2E 00 00

Production
Period:

16

4

0x 40 06 00 00

Reserved:

20

2

0x 00 00

Destination
Type:

22

2

0x 01 00

Destination
address

24

32

0x 69 66 00 C8
00 00 00 00 00
00 00 00 00 00
00 00 00 00 00
00 00 00 00 00
00 00 00 00 00
00 00 00

Configuration
State:

56

2

0x 02 00

Exchange
Length:

58

2

0x 78 05

Reserved:

60

4

0x 00 00 00 00

UDP/IP Port

64

2

0x 46 47

Configuration
Type:

66

2

0x 00 00

Configuration
Sig.:

68

2

0x 00 00

Mode:

70

2

0x 02 00

Reserved:

72

2

0x 00 00

Configuration
Data:

74

2

0x 00 00

This is an example of The Module's EGD Configuration Response to the
Command Production Data Unit.

This is the Hexadecimal representation of the Retrieve configuration Response
from the above table. It includes the Ethernet II, IPv4, UDP and within UDP the
EGD Server's Reply PDU Type 4 depicted in bold font.

00 12 3F AE 5C AE 00 0D 8D 00 13 83 08 00 45 00

00 68 00 04 00 00 FE 11 E8 1F 69 66 00 CD 69 66

00 C8 04 01 1F 01 00 54 EC F2 04 00 11 11 01 00

4C 00 69 66 00 C8 E1 2E 00 00 40 06 00 00 00 00

01 00 69 66 00 C8 00 00 00 00 00 00 00 00 00 00

00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00

00 00 02 00 78 05 00 00 00 00 46 47 00 00 00 00

02 00 00 00 00 00