MVI69-EGD ♦ CompactLogix or MicroLogix Platform

Reference

GE Ethernet Global Data Communication Module

Page 74 of 96

ProSoft Technology, Inc.

November 3, 2008

PDU Type = 35

Write Response.

The write response is returned from a destination controller in response to a write
request message. It serves as an acknowledgment for the original request. A
positive response indicates that all of the data has been written to the responding
device. An error response indicates that one or more of the transfers to the
responding device failed. Responders shall use all available means to assure
that a write is performed in its entirety or not performed at all. Requesting
applications are advised that if partial failures of the write can cause problems
with the control algorithm, they should include only one cell in each write to
assure complete knowledge of the disposition of the write request.

Packet
Info

Description Data

Source Port:

7937 (0x 1F01)

Destination Port:

7937 (0x 1F01)

Length:

xx bytes (0x 00 XX)

Checksum:

xxxxx (0x XX XX)

EGD's PDU Field:

Offset

Bytes

Hex code

PDU Type:

0

1

0x 23

Message Flag:

1

1

0x HH

Request ID:

2

2

0x HH HH

PVN1:

4

1

0x 01

Option Length:

5

1

0x HH

Message Length:

6

2

0x HH HH

Configuration
Signature:

8

2

0x HH HH

Address Type:

10

1

0x HH

Cell count:

11

1

0x HH

Producer ID:

12

4

0x HH HH HH HH

Exchange ID:

16

4

0x HH HH HH HH

Time Stamp:

20

8

0x HH . . . HH

UDP

EGD:

Reserved:

28

4

0x HH HH HH HH