ProSoft Technology MVI69-EGD User Manual

Page 82

Advertising
background image

MVI69-EGD ♦ CompactLogix or MicroLogix Platform

Reference

GE Ethernet Global Data Communication Module

Page 82 of 96

ProSoft Technology, Inc.

November 3, 2008

Normal Output Data Block

These blocks of data transfer information from the CompactLogix or MicroLogix
processor to the module and source the input (monitored) data to be used by the
remote master. The structure of the output image used to transfer this data is
shown in the following table.

Words Description

0 Block

write

ID

1 to n

Output data (60, 120 or 240 words)

where n = 60, 120, or 240 depending on the Block Transfer Size parameter (refer to the
configuration file).

The Write Block ID is an index value used to determine the location in the
module's database where the data will be placed. Each transfer can move up to
200 words (block offsets 1 to 200) of data.

5.2.7 Command Control Blocks

Command control blocks are special blocks used to control the module. The
current version of the software supports the following command control blocks.

Code Description

-1 or 0

Empty data blocks

1 to 20

Data read or write blocks

2000

C/P status data

9250

General status data

9998

Warm boot module (same effect as 9999)

9999 Cold

boot

module

Block 2000 Request

Words Description

0

2000 Command Block ID

1

Number of C/P messages (1 to 4)

2

First C/P index (0 to 99)

3 to n

Reserved

where n = 60, 120, or 240 depending on the Block Transfer Size parameter (refer to the
configuration file).

Block 2000 Response

Words Description

0

2000 Command Block ID

1

Block write ID requested

2

Number of C/P messages (0 to 4) Will be set to 0 if error in request.

3

First C/P index (0 to 99)

4 to 17

C/P Status Data

18 to 31

C/P Status Data

32 to 45

C/P Status Data

Advertising
This manual is related to the following products: