Mailbox Messaging
PTQ-PDPMV1 ♦ Quantum Platform
User Manual
PROFIBUS DP Master Network Interface Module for Quantum
Page 158 of 306
ProSoft Technology, Inc.
August 12, 2014
Example: To address Group 1, 2, and 4, the Group Select value should be D0h.
If an individual slave should be addressed, the correct group selection must also
be made, as the slave will ignore the message if it does not belong to the
requested group(s).
What group(s) a slave belongs to is determined during network configuration,
and is downloaded during initialization to each slave via the PROFIBUS telegram
Set_Prm.
Control Command
This parameter specifies the command to send:
Bit
Explanation
0 (LSB)
Reserved, set to zero
1
Reserved, set to zero
2
Unfreeze input data
3
Freeze input data
4
Unsynchronize output data
5
Synchronize output data
6
Reserved, set to zero
7 (MSB)
Reserved, set to zero
Combinations of the bits (Unsync/Sync and Unfreeze/Freeze
Bits 0 or 6
Bits 1 or 7
Explanation
0
0
No function
0
1
Function will be activated
1
0
Function will be inactive
1
1
Function will be inactive
Fault Information and Extended Fault Information
"Fault Information" Contents
"Extended Fault Information" Contents
0100h
Address out of range
-
0200h
Group number 0 not
permitted
-
0A00h
Failed to send Global
Control request
0A00h
Incorrect operation mode (CLEAR/OPERATE
only)
0150h
Invalid Freeze Group (Group is not initiated to be
Freeze Group)
0250h
Invalid Sync Group (Group is not initiated to be
Sync Group)
0350h
Incorrect Control Command
0450h
No Sync -/ or Freeze groups enabled in Master
configuration
FE00h
Command not
possible in Class 2
only mode
-
FF00h
Module not initialized
-