Data [1 … n]
Data that should be written.

Fault Information and Extended Fault Information
If "Invalid Other" is returned in the Message Information word in the header of the
response, information about the fault can be found here:

Fault Information

Extended Fault Information Contents

0100h

Address out of range

-

0A00h

Failed to execute request

Refer to Return Codes (page 181).

0B00h

Remote station failure

1000h

Remote station DPV1 failure

Function_Number

1100h

Length out of range (>240 bytes)

-

1200h

Slave does not support DPV1

-

1300h

Slave not active or not present in
configuration

-

FE00h

Command not possible in "Class 2-
Only" mode

-

FF00h

Module offline (not initialized or no
valid database)

-

Error Decode, Error Code 1, and Error Code 2
If "Fault Information" contains error code 1000h, more information according to
the DPV1 specification can be found here.

6.2.8 Mailbox Message: Alarm Indication

This mailbox message indicates to the application that a DPV1 slave has
transferred an alarm message to the Master. The message is sent spontaneously
by the module. That is, the module itself initiates the mailbox communications.

Detailed information about the cause of the alarm is presented in extended words
1 to 3 and in the message data field (see below).