ProSoft Technology PTQ-PDPMV1 User Manual

Page 260

Advertising
background image

Reference

PTQ-PDPMV1 ♦ Quantum Platform

User Manual

PROFIBUS DP Master Network Interface Module for Quantum

Page 260 of 306

ProSoft Technology, Inc.

August 12, 2014

Word
Offset

Name

Description

64 to 65 HSBY Passive PROFIBUS

CRC32
(Unity only)

CRC32 checksum for PROFIBUS Master configuration downloaded from

configuration utility via UDP

66 to 67 HSBY Passive User Cfg CRC32

(Unity only)

PTQ-PDPMV1 module configuration checksum for module configuration
downloaded from configuration utility via UDP

68 to 71 Reserved

Reserved for future use

72

Control Data

This word is used when Mailbox Messaging is disabled.
Operating State Mode Return (New)
Bit 15= Handshake bit
Bit 14= Error bit (1=Error, 0=No error)
Bits 12-13= Reserved for future use
Bits 8-11= Error code if bit 14 set:
(1=Queue full, 2=Memory allocation error, 3=Invalid operating mode

command)
Bits 0-7 contain the operation code requested:
0x40= Stop
0x80= Clear
0xC0= Operate

73

In Mailbox Queue Count

Number of message in the In Mailbox queue

74

Out Mailbox Queue Count

Number of message in the Out Mailbox queue

75

Alarm Queue Count

Number of message in the Alarm queue

76

Last Out Mailbox Message ID
Processed from Output Image

The module confirms the receipt of a mailbox by copying its ID code
(Message ID) to this register

77

Current In Mailbox Control Index Incremented after the module has transferred a new mailbox response to

the processor

78

Current Alarm Control Index

Incremented after the module has transferred a new alarm to the processor

Advertising