Word
Offset
Name
Description
64 to 65 HSBY Passive PROFIBUS
CRC32
(Unity only)
CRC32 checksum for PROFIBUS Master configuration downloaded from
configuration utility via UDP
66 to 67 HSBY Passive User Cfg CRC32
(Unity only)
PTQ-PDPMV1 module configuration checksum for module configuration
downloaded from configuration utility via UDP
68 to 71 Reserved
Reserved for future use
72
Control Data
This word is used when Mailbox Messaging is disabled.
Operating State Mode Return (New)
Bit 15= Handshake bit
Bit 14= Error bit (1=Error, 0=No error)
Bits 12-13= Reserved for future use
Bits 8-11= Error code if bit 14 set:
(1=Queue full, 2=Memory allocation error, 3=Invalid operating mode
command)
Bits 0-7 contain the operation code requested:
0x40= Stop
0x80= Clear
0xC0= Operate
73
In Mailbox Queue Count
Number of message in the In Mailbox queue
74
Out Mailbox Queue Count
Number of message in the Out Mailbox queue
75
Alarm Queue Count
Number of message in the Alarm queue
76
Last Out Mailbox Message ID
Processed from Output Image
The module confirms the receipt of a mailbox by copying its ID code
(Message ID) to this register
77
Current In Mailbox Control Index Incremented after the module has transferred a new mailbox response to
the processor
78
Current Alarm Control Index
Incremented after the module has transferred a new alarm to the processor